The CD8-G2 paging console is a remote paging interfaces with access level 2 protection, compatible with PRIMA VA systems.
It serves up to 8 individual zones with an all-call button. Zone selection buttons and fireman microphone are encased in a heavy-duty IP30 wall-mount metal box with a lockable door.
The CD8-G2 zone buttons can represent a single zone or group of zones and are easily programmed through the system GUI using "drag and drop" functionality. The Push-To-Talk button can be programmed for PTT or latching operation. System status indicators show the status of all zones and indicators are also provided for Power, Evac and Fault.
The CD8-G2 is powered over RS485 via CAT5 (FTP/STP), however if power is not available over RS485 it can be locally powered using a 24 VDC supply.
- Wall-mount heavy duty remote paging console with Access level 2 protection to comply with the EN54-16
- 8 zone selection buttons
- All-call button
- LED test button
- Power indicator
- EVAC indicator
- Status and Fault indicator
Electrical
- Power supply: RS485 (RJ45/CAT-5)
- DC / battery power requirements:
- Voltage: 18 - 26 VDC
- Power consumption: 120 mA
Audio
- Frequency response: -3 dB @ 200 to 8k Hz
- THD: < 1% @ 1k Hz
- Output level Max: 6 dBu
- Noise gate threshold: -84 dBu - 24 dBu
- Attack time: 8 ms
- Release time: 100 ms
- Monitoring speaker:
- Impedance: 4 Ohms
- Output power: 1 W @ 1k Hz
- Frequency response: -3 dB @ 200 to 12k Hz
- System connection:
- Cable type: CAT-5
- Length: 100 m
Environmental
- Operating temperature: -5 ºC ~ +55 ºC
- Storage temperature: -40 ºC ~ +70 ºC
- Relative humidity: 15% to 90%
- Air pressure: 600 to 1100 h Pa
- IP rating: 30
- Heat Dissipation: 10 BTU/hr
Mechanical
- Dimensions (W x H x D): 318.6 x 187 x 130 mm
- Weight: 3.6 Kg